Monostabiel relais voor zware toepassingen

SKU-short: OK
Merk:

Hoofdspecificaties

Monostable 4CO:10A & 4NO:10A relay for severe applications.

Product advantages

  • Breaking capacity adapted to inductive loads.
  • High reliability for intensive use in severe environments.
  • Extra-strong make contacts due to plunger core.
  • 8 or 12 contacts available on request.

Models

  • OK N 4 CO 10 A – general use.
  • OK Fc 4 CO 10 A – low consumption.
  • OK B184 4 CO 10 A – EDF-approved, built-in magnetic blow-out.
  • OK SCd 4 CO 10 A – for lighting circuit.
  • OK SGcCd 4 NO 10 A long travel – for heavy and inductive loads.
  • OK SFcUIC 4 CO 10 A – UIC-compliant for railway applications.

General specifications

  • Dielectric strength: 2000 V – 50 Hz – 1 min.
  • Insulation resistance (according to EN 61810): 1000 MO at 500 Vdc.
  • Voltage impulse: 5 kV – 0,5 J (1,2 / 50 µs).
  • Mechanical life span:
    • OK N: 20 x 10 6 operations
    • OKB184, OK SFcUIC: 50 x 10 6 operations
    • OK Fc, OK SCd, OK SGcCd: 100 x 10 6 operations
  • Operating temperature:
    • OK N, OK SCd: -25°C…+40°C
    • OK Fc, OK SGcCd: -25°C…+50°C
    • OKB184, OK SFcUIC: -25°C…+55°C
  • Storage temperature: -40°C…+85°C.
  • Relative humidity: standard version: < 80%.
  • Resistance to vibrations (according to EN 61810): 5 g from 5 to 60 Hz (1 min).
  • Resistance to shocks: 30 g – 11 ms – ½ sine.
  • Protection rating: IP 20 (IP40 on request).
  • Weight: 300 g (for 4 contacts).
  • Railway standards: NF-F 16-101, NF-F 16-102 (materials) UIC 616-0.
  • EDF standard: HM-2 A / 03 / 111 / A.
Toon meer
* Log in en krijg toegang tot uw voorkeursprijzen
Gegroepeerde productitems
REF Capaciteit Klasse Bescherming Spanning Gewicht prijs Voorraad
OKFC-110VDC 4 RT contacts 10A IP 20 110V DC 300 g
délai sur demande
OKN 4 RT contacts 10A IP 20 110V DC 300 g
délai sur demande
OKN--220VAC 4 RT contacts 10A IP 20 220V AC 300 g
délai sur demande
OKN-220VDC 4 RT contacts 10A IP 20 220V DC 300 g
délai sur demande
OKN-24VDC 4 RT contacts 10A IP 20 24V DC 300 g
délai sur demande
OKSCD 4 RT contacts 10A IP 20 24V DC 300 g
délai sur demande

Omschrijving

Monostable 4CO:10A & 4NO:10A relay for severe applications.

Product advantages

  • Breaking capacity adapted to inductive loads.
  • High reliability for intensive use in severe environments.
  • Extra-strong make contacts due to plunger core.
  • 8 or 12 contacts available on request.

Models

  • OK N 4 CO 10 A – general use.
  • OK Fc 4 CO 10 A – low consumption.
  • OK B184 4 CO 10 A – EDF-approved, built-in magnetic blow-out.
  • OK SCd 4 CO 10 A – for lighting circuit.
  • OK SGcCd 4 NO 10 A long travel – for heavy and inductive loads.
  • OK SFcUIC 4 CO 10 A – UIC-compliant for railway applications.

General specifications

  • Dielectric strength: 2000 V – 50 Hz – 1 min.
  • Insulation resistance (according to EN 61810): 1000 MO at 500 Vdc.
  • Voltage impulse: 5 kV – 0,5 J (1,2 / 50 µs).
  • Mechanical life span:
    • OK N: 20 x 10 6 operations
    • OKB184, OK SFcUIC: 50 x 10 6 operations
    • OK Fc, OK SCd, OK SGcCd: 100 x 10 6 operations
  • Operating temperature:
    • OK N, OK SCd: -25°C…+40°C
    • OK Fc, OK SGcCd: -25°C…+50°C
    • OKB184, OK SFcUIC: -25°C…+55°C
  • Storage temperature: -40°C…+85°C.
  • Relative humidity: standard version: < 80%.
  • Resistance to vibrations (according to EN 61810): 5 g from 5 to 60 Hz (1 min).
  • Resistance to shocks: 30 g – 11 ms – ½ sine.
  • Protection rating: IP 20 (IP40 on request).
  • Weight: 300 g (for 4 contacts).
  • Railway standards: NF-F 16-101, NF-F 16-102 (materials) UIC 616-0.
  • EDF standard: HM-2 A / 03 / 111 / A.